| DOW ENDURANCE™ HFDB-0586 BK is a specially formulated semiconductive, vulcanizable compound designed for use as an extruded conductor shield and bonded insulation shield applications in power cables.(1) DOW ENDURANCE ™ HFDB-0586 BK has stable volume resistivity characteristics at elevated temperatures and is formulated with a polymer system that has demonstrated compatibility with copper and aluminum conductors. DOW ENDURANCE™ HFDB-0586 BK offers outstanding extrusion properties with low melt pressures and low temperature generation that result in outstanding scorch resistance under a wide processing window. (1) DOW ENDURANCE™ HFDB-0586 BK is recommended for use in conjunction with DOW cross-linked polyethylene and tree-retardant cross-linked polyethylene compound. For other polymer insulations as well as EPR and EPDM the user is cautioned to establish the utility of DOW ENDURANCE™ HFDB-0586 BK with each formulation. Applications DOW ENDURANCE™ HFDB-0586 BK has been designed for semiconductive applications in power distribution and transmission cables for cables rated up to 150 kV. It can be used as inner and outer semiconductive layer for bonded cable applications and as inner semiconductive layer for strippable cable constructions. Contact your Dow representative for further recommendations. Specifications DOW ENDURANCE™ HFDB-0586 BK is designed for use in power distribution and transmission cables. Power cables with conductor and insulation shielding made of DOW ENDURANCE™ HFDB-0586 BK, prepared using sound, commercial fabrication practice, would be expected to meet the following cable specification(s): IEC: 60502-2 and 60840 HD: 620 S2 and 632 S2 BS: 6622 DIN: VDE 0273 and 0263 Edf: HN-33-S-23 and HN-33-S-52 AEIC: CS8, CS9 AEIC: ICEA: S-94-649, S-97-682, S-113-684, S-66-524 (NEMA WC7), S-108-720 GB/T 12706, GB/T 11017&& |
| Product Description | |
|---|---|
| Supplier | DOW |
| Generic | Ethylene copolymer |
| Material Status | Commercial: Active |
| Availabilitys | Europe |
| Technical Data | |||
|---|---|---|---|
| PHYSICAL | Nominal value | Unit | Test method |
| Density | 1.12 | g/cm³ | ISO 1183/D |
| water content | |||
| Karl Fischer | < 1000 | ppm | Internal Method |
| MECHANICAL | Nominal value | Unit | Test method |
|---|---|---|---|
| tensile strength | 20.0 | MPa | IEC 60811-1-1 |
| Tensile strain | |||
| fracture | > 200 | % | IEC 60811-1-1 |
| Aging performance | Nominal value | Unit | Test method |
|---|---|---|---|
| The rate of change in tensile strength | |||
| 150℃,240 hr | < 25 | % | IEC 60811-1-2 |
| Change rate of ultimate elongation | |||
| 150℃,240 hr | < 25 | % | IEC 60811-1-2 |
| THERMAL | Nominal value | Unit | Test method |
|---|---|---|---|
| thermosetting | IEC 60811-2-1 | ||
| Elongation under load: 200 ℃ | 50 | % | IEC 60811-2-1 |
| Elongation without load: 200 ℃ | 0.0 | % | IEC 60811-2-1 |
| Electrical performance | Nominal value | Unit | Test method |
|---|---|---|---|
| Volume resistivity | IEC 60093 | ||
| 23℃ | 40 | ohms·cm | IEC 60093 |
| 90 ℃ | < 1.0E+2 | ohms·cm | IEC 60093 |
| Supplementary information | Nominal value | Unit | Test method |
|---|---|---|---|
| Moving Die Rheometer | ASTM D5287 | ||
| Crosslinking time, T90: 182 ℃ | 5.4 | min | ASTM D5287 |
| Maximum Torque,MH:182℃ | 11.2 | dNm | ASTM D5287 |
| Coking time TS1:140 ℃ | 31.0 | min | ASTM D5287 |
| Process Conditions | |||
|---|---|---|---|
| Extrusion | Nominal value | Unit | Test method |
| Drying temperature | 60 | °C | |
| Drying time | 2.0 to 6.0 | hr | |
| Notes |
|---|
| 1. Typical properties: these are not to be construed as specifications. |
| 2. Measured on crosslinked compression moulded samples. |
| 【 Disclaimer 】 Guangzhou Soliao Information Technology Co., Ltd. reserves all rights. The information in this data table was obtained from the manufacturer of the material on soliao.com. Soliao.com makes every effort to ensure the accuracy of this data. However, the search company does not assume any responsibility for the uncertainty and consequences caused to users by these data values and suggestions, and strongly recommends verifying the data values with the material supplier before the final selection of materials. |