About |
---|
DOW ENDURANCE™ HFDC-4202 EC is a long-life, water-tree-retardant, unfilled, crosslinkable, low density polyethylene insulation compound. The permanent tree-retardant additive provides improved performance in power cables in service involving exposure to moisture while retaining the excellent physical, electrical, and processing attributes of conventional, crosslinkable polyethylene. DOW ENDURANCE™ HFDC-4202 EC compound provides electric utilities with: State-of-the-art “water” tree-retardant technology, consistently outperforming conventional XLPE in all accelerated cable wet aging tests at ambient and elevated temperatures Proven in the field for over 25 years, at a broad cross section of geographical conditions, demonstrating excellent reliability and help achieving lowest life cycle costs Excellent electrical performance demonstrated by very high aged electrical strength and very low aged dissipation factor and power loss. DOW ENDURANCE™ HFDC-4202 EC compound represents the state-of-the-art in tree-retardant, power cable insulation compounds. Specifications DOW ENDURANCE™ HFDC-4202 EC tree-retardant compound is designed for use in power distribution and sub-transmission cables, especially in underground applications. DOW ENDURANCE™ HFDC-4202 EC provides improved performance over XLPE cables and is recommended, with or without moisture barriers, for use as cable insulation up to and including 69 kV applications. Cables insulated with DOW ENDURANCE™ HFDC-4202 EC, using sound commercial fabrication manufacturing practice, would be expected to meet the latest editions of the following specifications and regulations: ANSI/ICEA: S-94-649, S-97-682, S-93-639 / NEMA WC74 (TR-XLPE requirements) AEIC: CS8 RUS 50-70 (U-1) CEA: WCWG-01, WCWG-02 UL 1072 IEC: 60502, 60840 CENELEC: HD 620 S1 DIN VDE 0276-620 BSI BS 6622 GB/T 12706 DL/T 1070&& |
Product Description | |
---|---|
Supplier | DOW |
Generic | LDPE |
Material Status | Commercial: Negative |
Availabilitys | North America,Latin America,Asia Pacific |
Technical Data | |||
---|---|---|---|
PHYSICAL | Nominal value | Unit | Test method |
Density | 0.920 | g/cm³ | ASTM D792 |
The degree of cross combination (Extractables) | < 20 | % | ASTM D2765A |
MECHANICAL | Nominal value | Unit | Test method |
---|---|---|---|
tensile strength | 22.1 | MPa | ASTM D638 |
Tensile strain | |||
fracture | 530 | % | ASTM D638 |
Aging performance | Nominal value | Unit | Test method |
---|---|---|---|
Tensile strength retention rate | ASTM D638 | ||
14 days:150℃ | > 75 | % | ASTM D638 |
30 days:121℃ | > 75 | % | ASTM D638 |
30 days:136℃ | > 75 | % | ASTM D638 |
Elongation retention rate | ASTM D638 | ||
14 days:150℃ | > 75 | % | ASTM D638 |
30 days:121℃ | > 75 | % | ASTM D638 |
30 days:136℃ | > 75 | % | ASTM D638 |
THERMAL | Nominal value | Unit | Test method |
---|---|---|---|
High temperature creep | |||
200℃ | < 100 | % | ICEA T-28-562 |
thermosetting | |||
200℃ | < 10 | % | ICEA T-28-562 |
Electrical performance | Nominal value | Unit | Test method |
---|---|---|---|
Volume resistivity | |||
23℃ | > 1.0E+15 | ohms·cm | ASTM D257 |
Dielectric strength | ASTM D149 | ||
3.18 mm | 26 | kV/mm | ASTM D149 |
3.18 mm | 23 | kV/mm | ASTM D149 |
Dielectric constant | |||
60 Hz | 2.30 | ASTM D150 | |
Dissipation factor | |||
60 Hz | 3.0E-4 | ASTM D150 | |
Water-Tree Growth Rate | 10 | % | ASTM D6097 |
Water-Tree Relative Size | 25 | % | ASTM D6097 |
Notes |
---|
1. Typical properties: these are not to be construed as specifications. |
2. Method A (Short-Time) |
3. Method B (Step-by-Step) |
4. Rate is relative to rate for Dow’s standard XLPE, FREQ = 1 kHz. |
5. Size is relative to size for Dow’s standard XLPE. |
【 Disclaimer 】 Guangzhou Soliao Information Technology Co., Ltd. reserves all rights. The information in this data table was obtained from the manufacturer of the material on soliao.com. Soliao.com makes every effort to ensure the accuracy of this data. However, the search company does not assume any responsibility for the uncertainty and consequences caused to users by these data values and suggestions, and strongly recommends verifying the data values with the material supplier before the final selection of materials. |