About |
---|
Description LUTENE® XL2808BK TR is specially designed cross-linkable semi-conductive compound for conductor shielding of medium voltage power cables. LUTENE® XL2808BK TR is compatible with both copper and aluminum conductors. LUTENE® XL2808BK TR was specifically developed to provide an excellent smoothness surface yielding a more perfect interface between extruded shield and the insulation. As a result, significantly improved cable performance can be expected. LUTENE® XL2808BK TR is recommended for use in conjunction with XL8080NTS (Cross-linked polyethylene compound) and XL8080TR (Tree-retardant cross-linked polyethylene compound) Applications Cross-linkable semi-conductive compound for conductor and bonded insulation shielding of medium voltage power cables with rated voltage up to 35kV Characteristics Excellent Surface Smoothness Excellent Electrical Properties Excellent Physical and Thermal Properties Long-run Extrusion without Scorch Specification LUTENE® XL2808BK TR meets the property requirement of the following material specifications. AEIC CS8 ICEA S-94-649, S-93-639 / NEMA WC74 IEC 60502 CENELEC HD620 BS 6622&& |
Product Description | |
---|---|
Supplier | LG Chemical |
Generic | PE |
Material Status | Commercial: Active |
Features | Good surface appearance,Conductive,Good Electrical Properties,Crosslinked |
Availabilitys | Africa & Middle East ,North America,Latin America,Asia Pacific,Europe |
Technical Data | |||
---|---|---|---|
PHYSICAL | Nominal value | Unit | Test method |
Density | 1.12 | g/cm³ | ASTM D1505 |
Moisture content | < 500 | ppm | Karl Fisher |
MECHANICAL | Nominal value | Unit | Test method |
---|---|---|---|
tensile strength | |||
yield | 17.7 | MPa | ASTM D638 |
Tensile strain | |||
fracture | 200 | % | ASTM D638 |
Aging performance | Nominal value | Unit | Test method |
---|---|---|---|
Tensile strength retention rate | > 90 | % | ASTM D638 |
Elongation retention rate | > 90 | ppm | ASTM D638 |
THERMAL | Nominal value | Unit | Test method |
---|---|---|---|
Embrittlement temperature | < -50.0 | ℃ | ASTM D746 |
Heat Deformation | < 18 | % | JIS C3005 |
Electrical performance | Nominal value | Unit | Test method |
---|---|---|---|
Volume resistivity | ASTM D991 | ||
23℃ | < 50 | ohms·cm | ASTM D991 |
90 ℃ | < 5.0E+2 | ohms·cm | ASTM D991 |
135 ℃ | < 1.0E+3 | ohms·cm | ASTM D991 |
Supplementary information | Nominal value | Unit | Test method |
---|---|---|---|
Ion content | |||
Metal | < 300 | % | Internal Method |
Process Conditions | |||
---|---|---|---|
Extrusion | Nominal value | Unit | Test method |
Drying temperature | 60 to 70 | °C | |
Drying time | 4.0 | hr | |
Melt temperature | 100 to 125 | °C |
Notes |
---|
1. Typical properties: these are not to be construed as specifications. |
2. 23°C |
3. 7.9 in/min |
【 Disclaimer 】 Guangzhou Soliao Information Technology Co., Ltd. reserves all rights. The information in this data table was obtained from the manufacturer of the material on soliao.com. Soliao.com makes every effort to ensure the accuracy of this data. However, the search company does not assume any responsibility for the uncertainty and consequences caused to users by these data values and suggestions, and strongly recommends verifying the data values with the material supplier before the final selection of materials. |