| About |
|---|
| UNIGARD™ HP HFDA-6522 Natural is a flame retardant vulcanizable polyethylene copolymer based wire insulation material. It is recommended for use in 600 volt power cable and control cable applications and is suitable for 90°C service in wet locations. Specifications HFDA-6522 Natural is Bulletinized by Underwriters Laboratories requirements for use in XHHW, XHHW-2, XHH, RHH, RHW, RHW-2, SIS, USE, USE-2 applications, and VW-I.(a) This compound is also suitable for the Canadian Standards Association NMD-90 and RW-90 applications.&& |
| Product Description | |
|---|---|
| Supplier | DOW |
| Generic | PE copolymerization |
| Material Status | Commercial: Active |
| Availabilitys | Africa & Middle East ,North America,Latin America,Asia Pacific,Europe |
| Technical Data | |||
|---|---|---|---|
| PHYSICAL | Nominal value | Unit | Test method |
| Density | 1.30 | g/cm³ | ASTM D1505 |
| Mechanical water absorption rate | |||
| 82℃ | 0.190 | mg/cm² | UL 1581 |
| MECHANICAL | Nominal value | Unit | Test method |
|---|---|---|---|
| tensile strength | 13.8 | MPa | ASTM D638 |
| Tensile strain | |||
| fracture | 330 | % | ASTM D638 |
| Bending modulus | |||
| 1% secant | 124 | MPa | ASTM D790 |
| Aging performance | Nominal value | Unit | Test method |
|---|---|---|---|
| Tensile strength retention rate | |||
| 7 days,121℃ | 100 | % | ASTM D638 |
| Elongation retention rate | |||
| 7 days,121℃ | 95 | % | ASTM D638 |
| THERMAL | Nominal value | Unit | Test method |
|---|---|---|---|
| deformation | |||
| 121℃ | 10 | % | UL 44 |
| Electrical performance | Nominal value | Unit | Test method |
|---|---|---|---|
| Dielectric constant | |||
| 60 Hz | 3.20 | ASTM D150 | |
| Dissipation factor | |||
| 60 Hz | 3.0E-3 | ASTM D150 | |
| SIC | UL 44 | ||
| in 75℃(167°F) water,after 24 hrs | 3.23 | UL 44 | |
| in 75℃(167°F) water,increase,1 to 14 days | 2.0 | % | UL 44 |
| in 75℃(167°F) water,increase,7 to 14 days | 0.10 | % | UL 44 |
| Stability Factor | 0.300 | UL 44 | |
| insulation resistance | |||
| in water,16℃ | 50000 | Mohms/1000 ft | UL 44 |
| FLAME CHARACTERISTICS | Nominal value | Unit | Test method |
|---|---|---|---|
| Extreme oxygen index | 29 | % | ASTM D2863 |
| VW-1- Vertical Combustion Test (No. 14 AWG (1.63 mm dia.) XHHW, RHH) | Pass | UL 44 | |
| Flame test | |||
| Horizontal | Pass | UL 44 |
| Notes |
|---|
| 1. Typical properties: these are not to be construed as specifications. |
| 【 Disclaimer 】 Guangzhou Soliao Information Technology Co., Ltd. reserves all rights. The information in this data table was obtained from the manufacturer of the material on soliao.com. Soliao.com makes every effort to ensure the accuracy of this data. However, the search company does not assume any responsibility for the uncertainty and consequences caused to users by these data values and suggestions, and strongly recommends verifying the data values with the material supplier before the final selection of materials. |